670459
3
Zoom out
Zoom in
Previous page
1/21
Next page
CE1G2406E 3
5.1 Plant diagram VG0
Heating circuit control with heating circuit pump, d.h.w. control with second heat transfer station and preheating.
5.1.1 Recommended components
Fast-running actuator for valve Y11: SKD32.21; SQS35.53
Temperature detector B11: must be very fast
(use immersion type detector with no pocket!)
Temperature detector B3: required for fast controlled systems (fast heat exchangers)
5.1.2 Parameter settings group C - „General parameters“
No. Function Recomm.
setting
Range
Remarks
Unit Values set
C1 Type of plant 0 0…6
Acc. to plant diagram
VG…
C2 Bus address 0 0
1…7
15
Standalone
Slave
Master
C3 Set value boost (H-bus master) 10 0...15 °C
C4 Pump overrun time 4 0…7.5 min
C5 Display 1 0
1
Outside temperature
Time of day
C6 Pump Q1 0 0
1
Heating circuit pump
Main pump
C7 H4 function 0 0
1
Ymin function
Min. flow temperature
acc. to U4
C8
Not used
-
C9
Not used
-
5.1.3 Parameter settings group F - „Heating circuit“
No. Function Recomm.
setting
Range Remarks Unit
Values set
F1 Min. limitation of flow temperature 8 8…119.5 °C
F2 Max. limitation of flow temperature 95 8…119.5 °C
F3 Room temperature detector 1 0
1
Passive
Active
F4 Room temperature compensation 4 0
1…15
Passive
Active
F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for poorly insu-
lated buildings
F6 Switching differential room temperature limitation with room
unit
0 0…15 ¼ °C
F7 Type of building structure 1 0
1
Heavy
Light
F8 Adaptation of heating curve 0 0
1
Passive
Active
F9 Frost protection for the plant 1 0
1
Passive
Active
F10 Max. forward shift for optimum start control 0 0
10…150
Passive
Active
min
F11 Max. forward shift for optimum stop control 0 0
10…150
Passive
Active
min
F12 ECO extension 0 0…150 min
F13 Room set value boost with boost heating 5 0…15 °C
2406S11 / VG0
B1
B71
B9
Y1
B7
A6
M1
M5
B3
B11
Y11
B31
T
T
T
T
T
T
T
T
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens SIGMAGYR RVP97 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens SIGMAGYR RVP97 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info