2 CE1G2406E
3. Functional check
1. DO NOT switch on power yet!
2. With wall mounting: separate controller from the
base.
With flush panel mounting: separate terminal strips
from the controller.
3. Check wiring to make certain it is in compliance
with the plant wiring diagram.
4. Fit controller or terminal strips, depending on the
method of installation.
5. Check the regulating unit: Seat or slipper valve:
Ensure it is correctly fitted (observe direction of
flow indicated on the valve body)
Make certain the slipper operates in the correct
range (note position indicator)
Ensure the manual adjuster is disengaged
6. Note with underfloor and ceiling heating systems:
the limit thermostat must be correctly set. During
the functional check, the flow temperature must not
exceed the max. permissible level (usually 55 °C).
If that is the case, proceed immediately as follows:
Close the seat or slipper valve manually
Switch off the pump
Close the pump isolating valve
7. Switch on power.
The display must show something (e.g. the time of
day). If that is not the case, the cause is probably
one of the following:
No power
Main fuse blown
Manual switch not in position ΙΙ
3.1 Detector test
The detector test or the display of the actual tempera-
ture is activated by pressing the TEMP button. Press
TEMP several times. First, the 5 adjusted set value
temperatures appear, then the 8 following temp.:
Display Detector VG1-
VG6
VG0
TEMP 1 D.h.w. temperature detector 1 /
Primary return temp. detector 2
Remote telephone switch
B31 B11
TEMP 2 D.h.w. temperature detector 2
Secondary return temp. detector 2
B3 B3
TEMP 3 Primary return temperature detector B7 B7
TEMP 4 Secondary return temperature detec-
tor / D.h.w. charging detector
B71 B71
TEMP 5 Secondary flow temp. detector B1 B1
TEMP 6 Flow temp. detector heating circuit
Flow temp. detector d.h.w. circuit
Primary return temp. detector 2
B11 B11
TEMP 7 Outside detector B9 B9
TEMP
8 Room temperature detector A6 A6
Check:
If, in case of display of an actual temperature, o o o
appears in place of the temperature, the respective
detector has a short-circuit.
If, in case of display of an actual temperature, - - - ap-
pears in place of the temperature, the respective de-
tector is not connected.
The detector test mode can be quit either immediately
by pressing one of the operating mode buttons, or
automatically after about eight minutes.
3.2 Relay test
Button
Display Relay Effect
0
+
Relay test mode
active
1
+
Q1 Heating circuit
pump 1 on
2
+
Q3 /
Y3
D.h.w. charging
pump on
3
+
Q4 Storage tank
charging pump
on
4
+
Q5 D.h.w. circulating
pump on
5
+ 5:XX
5:XX
5:XX
Y1
Y2 Control valve
opens
Control valve
closes
6
+ 6
6
6
Y11
Y22
Valve opening
Valve closing
The relay test mode can be quit immediately by
pressing any of the operating mode buttons, or auto-
matically after about eight minutes.
Note:
Test step 5
XX = valve position according to stroke model (in %)
Terminal Y4 is always under voltage when Q3/Y3 is
deenergized!
4. Enduser settings
These are settings that can be made to meet individual
needs. They are directly accessible from the user inter-
face. For procedure, please refer to the operating in-
structions supplied with each controller.
5. Installer settings
These are plant-related settings that should only be
changed by the heating installer. They are subdivided
into different groups that can only be selected by
pressing combinations of buttons (please refer to the
table below).
The display shows the selected group, the parameter
and the adjusted value.
Combination of
buttons
Function
1
+
Selecting group C, F or H
2
+
5 Sek.
Selecting group U
Note: first, select button combination 1
3
+
+
Selecting the parameters of the group
Note: forward and reverse selection
possible
4
Adjusting the values
The parameter setting level can be quit either imme-
diately by pressing one of the operating mode buttons,
or automatically after about eight minutes.
Factory-set parameters:
Plant diagram VG1
2


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens SIGMAGYR RVP97 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens SIGMAGYR RVP97 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info