CE1G2406E
SIGMAGYR
®
RVP
Installation and Commissioning RVP97...
1. Notes
1.1 Place of installation
In a dry space (e.g. the boiler room), on a control
panel or control panel rail, on the control panel fa-
cia or in the sloping front of a control desk.
The controller must not be exposed to dripping
water.
Permissible ambient temperature: 0...50 °C.
1.2 Electrical installation
The local standards and regulations for electrical instal-
lations must be observed.
Cable tension relief must be ensured.
The wires from the controller to the actuator and the
pumps carry mains voltage.
The wires from the controller to the detectors carry
protective low voltage.
The permissible cable lengths for all detectors are
the following:
Copper cable 0.6 mm dia. 20 m max.
Copper cable 1.0 mm
2
80 m max.
Copper cable 1.5 mm
2
120 m max.
The cables to the detectors should not be run paral-
lel to mains carrying cable (e.g. power supply for
the pumps).
2. Installation and wiring
2.1 Wall mounting
1. Separate base from the controller by loosening the
two fixing screws on the front of the controller
(Fig. 1).
2. Fit base to the wall (Fig. 2) or to a DIN mounting
rail (Fig. 3).
3. Wire base according to the plant wiring diagram.
4. Place the controller on the base and secure by
tightening the two fixing screws on the front of the
controller.
2.2 Flush panel mounting
1. Separate base from the controller by loosening the
two fixing screws on the front of the controller
(Fig. 1).
2. Remove terminal strips from the base (Fig. 4).
3. Wire the terminal strips. Make certain the cables
will be sufficiently long, allowing the control panel
door to be opened and the wired terminal strips to
be moved about.
4. Introduce terminal strips through the panel cutout
and plug them into the controller (Fig. 5). In that
case, the base will no longer be required.
5. Place controller in the panel cutout and secure
(Fig. 6).
Note
: tighten the fixing screws only slightly!
1
2
3
4
56
1


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens SIGMAGYR RVP97 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens SIGMAGYR RVP97 in the language / languages: English as an attachment in your email.

The manual is 0,51 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info