Installation manual: Oasis security system JA-80K - 5 - MKE51801
Communicator connector – allows the connection of an
optional communicator to the main board.
Internal wiring connector – connects the internal wiring in the
control panel housing.
Terminals:
AC 20V the transformer output is connected here.
01, GND, 02 are hard-wired inputs for the control panel.
The reactions to triggering these inputs are determined by the
settings of addresses 01 and 02. The factory-set natural
reaction for these hard-wired inputs is a delayed alarm in
section C.
Terminals 01 and 02 use resistors in connected double
balanced loops to sense loop stand-by, activation or
tampering as follows:
o Connected to GND via a 1 kΩ resistor = untriggered input
o Connected to GND via 2 to 6 kΩ = triggered input,
o Connected to GND via less then 700Ω or more then 6 kΩ
= tamper signal
o Stand-by (untriggered) input zone must have 1 kΩ
o Up to five normally-closed door/window contacts can be
connected in series to enable one hard-wired input to be
used for multiple contacts with each contact having a 1kΩ
resistor in parallel (see the diagram below).
o Multiple normally-closed tamper contacts should be
connected in series without any parallel resistors. The
number of tamper contacts is unlimited and can be
combined with trigger contacts having parallel resistors (see
the diagram below).
o For wiring examples, see the below diagram.
o If you enroll a wireless device to address 01 or 02, the
corresponding input terminal will be disabled.
o If you do not use an input terminal and you do not enroll a
wireless device to its address, then the terminal must be
connected to the GND terminal via a 1 kΩ resistor.
NC normally closed contact for the external warning relay.
NO - normally open contact for the external warning relay.
EWC – common contact for the external warning relay max.
relay contact rating: 1A/60V. The control panel also transmits
the external warning relay signal via radio for wireless sirens.
IW – internal warning (siren) output. This output is grounded
during an internal alarm. A standard siren can be wired between
terminals +U and IW (max. 0.5A).
The IW output status is also
transmitted by radio for the IW siren.
The main difference between internal and external warning is during
the entrance delay period. If any instant detectors are triggered during
the entrance delay period, e.g. a child running straight to the living
room, only an internal warning will be triggered and an external
warning will only follow if the entrance delay has been exceeded.
PGX, PGY – are a pair of terminals providing programmable
outputs. If an output is activated it switches to GND with a
maximum load of 0.1A/12V. The factory-default setting of PGX is
the function ON/OFF which can be operated from the keypad by
the instruction 81 / 80 or using keys
). The factory-default
function of PGY is that it will be activated if any section of the
system is set. The status of PG outputs is also transmitted by
radio for AC and UC output modules.
GND – common ground connection
A,B – digital bus data
+U – back-up power supply (10 to 14V), 1A fuse. Max.
continuous load 0.4 A (max. intermittent load 1 A, for 15
minutes, once an hour). If the 1A fuse is blown, the control panel
will indicate power supply fault.
5. Wired keypad connection
GND A B U+
IN
+U
B
A
GND
GND
control and programming
keypad JA-80E
modular connection
cable
The control panel can be operated and programmed by JA-
80F wireless keypads and/or a JA-80E hard-wired keypad. A
hard-wired keypad can be connected to the control panel either
by flat telephone cable (max. length 10 metres) using RJ
connectors, or via twisted-pair cable (max. length 100 metres)
connected to the digital bus terminals (GND, A, B, +U).
We recommend only having a single JA-80E hard-wired
keypad in the system.
6. Back-up battery
It is possible to use a Jablotron-brand 12V back-up battery in
the control panel with capacities of 1.3Ah or 2.6no Ah. The
capacity to use depends on the total power consumption of the
system and the desired back-up period.
Euro-standard EN 50131-1 specifies a 12 hour minimum back-
up time for grade 2 systems. The standby consumption of all
system devices is shown in table 1.
Table 1- standby consumption of system devices
With a 1.3Ah back-up battery 12 hours of back-up time can be realised if
current consumption does not exceed 85mA. With 2.2Ah batteries
150mA should not be exceeded to achieve the same. This only takes
80% of the battery capacity into account as 20% has to be reserved for
battery aging effects.
The average back-up battery lifetime is up to 5 years after which it must
be replaced. The back-up battery is automatically charged and its
condition is monitored by the system. If the system is being run on only
the back-up battery a technical alarm occurs when the battery is
nearly discharged. If the voltage gets too low the battery will be
Device mA Note
Control panel JA-80K 50 No communicator
Keypad JA-80E 30
Keypad JA-80H (N) 60 Including a WJ-80 interface
Communicator JA-80Y 35
Communicator JA-80V 30
Wireless devices are not powered from the control panel.
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Jablotron JA-80K at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Jablotron JA-80K in the language / languages: English as an attachment in your email.

The manual is 0,55 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Jablotron JA-80K

Jablotron JA-80K User Manual - English - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info