Calling up information about the system
CS200 – 6720830474 (2015/06)
5.1.3 Thermal disinfection
WARNING:
Risk to life from legionella!
Legionella can form in domestic hot water at DHW
temperatures that are too low.
Activate thermal disinfection/daily heat-up.
Observe the statutory regulations on drinking water.
Have thermal disinfection/daily heat-up set in the service
menu by the installer.
WARNING:
Risk of scalding!
If thermal disinfection or the daily heat-up has been activated to
avoid legionella, the DHW is heated once to in excess of 60 °C
(e.g. Tuesday night at 02:00).
Only carry out thermal disinfection/daily heat-up outside
normal hours of use.
Make sure that a thermal mixer is installed. If in doubt, ask
your installer.
Thermal disinfection or daily heat-up safeguards the hygienic
quality of the domestic hot water. The domestic hot water is
heated regularly to the set temperature. This also kills off
legionella for example. Thermal disinfection must be set at the
control of the heat source (i. e.boiler).
Following thermal disinfection, the cylinder content slowly
cools back down to the set DHW temperature. Consequently,
the DHW temperature may briefly be higher than the set
temperature.
If a DHW cylinder is connected downstream from a low loss
header, it might not be possible to reach the temperature
necessary for thermal disinfection. For more information,
consult your contractor.
Menu: Thermal disinfection
Table 4 Settings for thermal disinfection
5.2 General settings
No settings are lost in the event of a brief power failure or if
power supply is shut down for short periods of time. When the
power supply is restored, the solar controller resumes
operation. If the shutdown period is prolonged, the date/time
settings may have to be reset. All other settings are maintained.
Menu: Settings
Table 5 General settings
Setting the time correction correctly (Time correction)
Example for calculating the time correction value, with a time of
day deviation of approx. – 6 minutes per year (the clock in the
solar controller is 6 minutes slow):
– 6 minutes per year = – 360 seconds per year
1 year = 52 weeks
– 360 seconds: 52 weeks = – 6.92 seconds per week
Increase the value of the time correction by 7 seconds per
week.
6 Calling up information about the system
The current system values and the active operating conditions
can be displayed easily via the info menu. No changes can be
made in this menu.
Menu item Description
Start The entire DHW volume is only heated to the
set temperature once a week or daily, if Auto
is set here.
Start now/
Cancel now
Immediate start or termination of thermal
disinfection independently of the set day of
the week
Temperature Temperature of the entire DHW volume
during thermal disinfection (65 ... 80 °C)
Day Day of the week, on which thermal
disinfection is automatically carried.
Alternatively, set daily thermal disinfection
Time of day Time of day for the automatic start of thermal
disinfection
Menu item Description
Language Language of the display texts
Time The time of the day can be set in this menu.
Date The date can be set in this menu.
Autom. time
changeover
Activate or deactivate the automatic
changeover between summer and winter
time. If Yes is set, the time of day is
automatically changed (from 02:00 to
03:00 on the last Sunday in March and
from 03:00 to 02:00 on the last Sunday in
October).
Display contrast Change the contrast (for improved clarity)
Time correction Time correction of the solar controller's
internal clock in s/week ( see below)
Menu item Description
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch CS 200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch CS 200 in the language / languages: English as an attachment in your email.

The manual is 1,23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Worcester-Bosch CS 200

Worcester-Bosch CS 200 Installation Guide - English - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info