28
It may take a full hour or longer to learn flows for
an entire 42-station controller. Each station may
take from 35 seconds to 5 minutes to be learned,
depending on stability of the flow.
Step 5: Review And Edit Flow
The flow values and settings for each station can be
reviewed, and manually edited, at the Set Flow Monitoring
dial position. It is important to verify the flow settings for
each station before leaving the controller in automatic
operation.
Turn the dial to the Set Flow Monitoring position.
Use the up and down arrows to navigate through all
stations, and verify that they have a learned flow or a
Not Monitored setting.
Do not leave any station with a Not Learned message-
either enter a flow manually, or set it to Not Monitored.
To edit a station's flow data, turn the dial to any other
position, hold down the Information button, and turn
the dial back to the Set Flow Monitoring position.
Select "EDIT LEARNED FLOW."
Use the up and down arrow buttons to move through
each station.
Use the +/- buttons to adjust the flow. Each station
can be set from 0.5 GPM (1.9 LPM) to 999.5 GPM
(2770LPM) in 0.5 GPM /1.9 LM increments. Between
the highest value (999.5) and the lowest (0.5/1.9
LPM), the Not Learned and Not Monitored choices
also appear, as the +/- buttons are pressed.
You can manually replace a Learned flow with another
value, if you wish.
LIMIT: Use the left and right arrow buttons to move to
the Limit field (LMT) to edit it, if desired.
The default Limit is always 115%, meaning the station
must exceed the flow by 15% before it will be treated
as an alarm (to prevent false alarms due to normal flow
fluctuations). 110% is the minimum possible Limit
setting, and 300% is the maximum.
DELAY: Use the left and right arrows to move to the
Delay setting to edit it, if desired.
The default delay is 01:00 in minutes:seconds format. This
means the station’s flow will be ignored for the first 1:00
of operation, before the flow will be considered for alarm
purposes. The Delay can be set from 0:15 to a maximum of
9:59. Some delay is recommended to prevent false alarms,
particularly when stations are initially activated.
You can Copy and Paste to edit flow settings for multiple
stations with similar characteristics. Select the station
with the Flow you wish to copy and press the Copy button.
You may then Paste (Paste button) the flow value into any
other stations.
The Limit and Delay settings may also be copied and
pasted together, separately from the Flow Value.
Review all stations to verify their flows, limits, and
delays.
Once station flows have been learned, flow monitoring
is in effect. If the Information button is pressed during
irrigation, the actual flow will be shown, along with
the combined limit of all active stations.
Stations that do not operate irrigation devices,
and stations that are not used, must be set to Not
Monitored to avoid false alarms.
FLOW ALARMS
When a Flow Alarm has been detected, the controller will
begin diagnostics, which can be seen in the display.
The controller will shut down all station activity for 1 full
minute. The display will show the stations as Paused
during this interval.
The controller will then test each station that was running
at the time of the alarm, individually. It will start the
lowest-numbered station that had been running, and allow
it to run for the Delay period set in Set Flow Monitoring.
After the Delay has elapsed, it will sample the flow rate, to
see if it is within the Flow Limit.
35

Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Hunter ACC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Hunter ACC in the language / languages: English as an attachment in your email.

The manual is 7,53 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Hunter ACC

Hunter ACC User Manual - German - 108 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info