EXTERNAL SENSOR CONNECTION
No external sensor is connected; after connection to the heating system, the
thermostat measures the room temperature with the internal sensor.
In this case, CONST10 is not set!
Once the external sensor is connected to the connector (page 3), perform
RESET (by simply pushing the RESET button). Verify correct connection of
the sensor:: CONST10 has the CI:d2 message and the sign. How-
ever, do not set the temperature with CONST10!
The temperature is measured with an external sensor. The advantage is that you can
measure the temperature in a different room from that in which the thermostat is located
(regulation of water, floor temperature, technological processes, etc.). With CONST2
(page 8), you can set a different maximum temperature within the range 15 to 99.5 °C.
Note: After disconnecting the external sensor, you must perform RESET again; thus you
re-activate the internal sensor.
You can choose the following functions of the BPT37 thermostat:
- regulation by the temperature measured by the internal sensor of the thermostat
- regulation by the temperature measured by the external sensor of the thermostat
- regulation by the temperature measured by the internal sensor with correction of the maximum
temperature of the thermostat external sensor (floor heating)
1, Function – internal sensor
2, Function – external sensor
BPT37 monitors the maximum floor temperature and simultaneously controls the room temperature. The
thermostat (with PI regulation) regulates the room temperature by the internal sensor (standard ther-
mostat function).
- Connect the external sensor (see page 3), which monitors the maximum
floor temperature.
- Perform RESET, the Ci:d2 message and sign appears with CONST10
(indicating correct connection).
- with CONST10 set the maximum floor temperature at which the
thermostat should switch off. If the room temperature reaches the
maximum permitted value, the heating device is switched off even if the
measured room temperature has not reached the required value. When
the external sensor temperature drops by 0.5 °C, the heating device is
switched on again.
It is necessary to set the maximum external sensor temperature (see CONST10, page 9).
To ascertain the current temperature of the internal and external sensor,
you can use the button; the display consecutively shows Cld:LO 1
(for internal sensor temperature) or Cld:LO 2 (external sensor tempera-
ture).
+/- H
Delivered sensor types:
CT01 C 10kΩ conductor CYXY 2*0.5 mm, length 1.5 m, metal case, for measurements up to 70 °C.
CT01 S 10kΩ silicon conductor, length 1.5 m, metal case, for measurements up to 99 °C.
CT01 P 10kΩ conductor CYXY 2*0.5 mm, length 1.5 m, PVC plastic case, submersible into liquid up to 70 °C.
THE SENSOR CONDUCTORS MUST NOT RUN PARALLEL WITH POWER CONDUCTORS!
3, Function – internal and external sensor = floor heating
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elektrobock BPT37 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elektrobock BPT37 in the language / languages: English as an attachment in your email.

The manual is 0,7 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info