L:\Bedienanleitungen\SOREL\DR1\DR1_mb_englisch_100903.p65
Solar Differential Controller DR1
Installation and Operating Instructions
running hours counter / adjustable: solar protection function, storage tank Tmax, degree-accuracy / sensor monitor /
digital LED display / 2-3 PT1000 temperature sensor inputs / 1 relay output with switch-over contact.
1. Description of the Controller
The LEDs on the front panel of the DR1
controller indicate the current
operational status of the system,
whereat the red LED 0 is used as the
standby light and the green LED
displays whether the relay R1 has
switched on the solar pump.
The yellow LED points out that the
temperature at sensor S2 in the solar
storage has exceeded the adjusted value
Tmax.
The temperature values of the connected
2-3 sensors are shown through the
commutator ‘S1 S2 S3’ on the LED display.
The display of service data and the solar
operating hours facilitate the function
control of the controller.
In case of a sensor defect the red LED
flashs a signal!
The required degree-accuracy, the
requested storage temperature and
optionally the switching-on temperature
of the solar protection are adjustable at
three red setting buttons ( potis ).
PT1000 sensor - with guaranteed
degree-accuracy according to DIN
43760 - provide for precise detection of
the temperature difference, which
guarantees the controlled switching
characteristics within the entire operati-
ve range.
Consequently, the conditions for an opti-
mal use of solar energy is ensured with
the DR1 controller.
3. Operating Modes
Through the operating modes switch, the
solar control is manually changeable:
0 = off, Auto = normal operation, = R1 on
Note: The position of the slide switch =
pump continuous operation may only be
switched on under supervision of the
specialist for control or adjustment works
- red LED flashing!
4. Settings
On the back-side of the pluggable
controller module, a red switch is located,
whose arrow is adjusted
to the requested degree-
Examples for application:
2. Description of the Functions
The Controller DR1 compares the
collector temperature at sensor S1 with
the storage temperature at sensor S2. If
the adjusted degree-accuracy S1/S2 is
exceeded, the relay R1 switches the so-
lar pump on to collect the solar heat.
If the degree-accuracy drops below the
half of the adjusted value, the solar pump
is switched off.
If the adjusted Tmax value is exceeded in
the lower storage range at S2, the solar
pump is switched off by R1, independent
of the degree-accuracy.
To extend the service life of the solar
control, the controller DR1 is equipped
with an adjustable solar protection
function. When the selected temperature
value is exceeded at the collector, R1
switches the solar pump on, until the
temperature at the collector has dropped
for 10K. At this it should be noted, that the
storage is heated up over the adjusted
Tmax value!
To protect the storage, the solar protection
function is switched off, if the temperature
at storage sensor S2 has reached 95°C.
Aus
130
110
70
90
Solarschutz S1/°C
T S1- S2 /°C
16
14
12
10
8
6
4
accuracy value S1/S2
of 4-16K by means of a
screwdriver.
( suggestion: 10K )
Through the second switch on the back-
side, the activation of the solar protection
function is specified.
By turning the adjusting
arrow to the left onto ‘off’,
the solar protection
function is switched off.
In the scaled range of
60-130°C, the activation of the solar
protection function is selectable.
( Suggestion: 110°C or ‘off )
After attaching the controller module onto
the base plate, the value for solar storage
charge Tmax of 20-90°C has to be
adjusted. ( suggestion: 60°C )
( hysteresis: 20-39°C=1K, 40-90°C=4K )
5. Service Values
Continuous display through shifting the
operating mode switch to ‘Auto’:
P = parameter resp. adjust values
F = sensor values
H = operating hours of the solar pump.
Subject to technical changes. Illustrations do not claim completeness.
Manufactorer: SOREL GmbH Mikroelektronik, Jahnstraße 36, D-45549 Sprockhövel, Tel.: 0049 23 39 / 60 24, Fax: 0049 23 39/6025
Tmax
R2 0I
Auto
S1 S3S2
20
30
40
50
60
70
80
90
0
DR 1
Tmax
°
C
Differenzregler
S2
S1
R1
S3
R1
S1
S2
1


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel DR2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel DR2 in the language / languages: English as an attachment in your email.

The manual is 0.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel DR2

Sorel DR2 User Manual - German - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info