4/20 2015-03-06 CE1G3333xx Siemens Building Technologies
Operating action:
Where? What?
DIP switch block,
switches no. 1 and 2
1 2
Heating and cooling in sequence
Two-stage heating
Single-stage cooling
Single-stage heating
Control mode and integral action time:
DIP switch block,
switches no. 3 and 4
3 4
P-mode
PI mode, integral action time = 120 s
(MEDIUM)
PI mode, integral action time = 240 s
(SLOW)
PI mode, integral action time = 60 s (FAST)
Test mode:
DIP switch block,
switch no. 5
5
Test mode
Normal operation
Outside temperature compensation:
DIP switch block,
switch no. 6
6
HIGH
LOW
P-band Y1
Potentiometer no. 5
Potentiometer setting should correspond to the re-
quired range of the controller’s output signal
P-band Y2
Potentiometer no. 4 Potentiometer setting should correspond to the re-
quired range of the controller’s output signal
Setpoint increase / decrease:
Slider 3
Setpoint or limit value:
Temperature
setting slider 5
Adjust after commissioning
Indication of operating state
The red LED indicates the controller’s operating state:
LED lit: Mains voltage present
LED flashes: In test mode
The LED is also visible when the cover is fitted.
Commissioning
When used as a controller
1. Remove housing cover.
2. Lift flexible plastic cover so that you can access the
setting elements.
3. Make the settings:
Operating mode (switches no. 1 and 2)
Control mode and (with PI mode) integral action
time (switches no. 3 and 4)
Test mode: Switch no. 5 =
Outside temperature compensation (when using an
outside sensor)
P-band Y1 (potentiometer 5) and Y2 (potentiome-
ter 4)
Setpoint increase or decrease (slider 3)
4. Replace flexible plastic cover.
5. Switch power on. LED for the operating state must
flash (test mode).
6. First, set temperature setting slider to the minimum
value, then to the maximum value: Actuating device(s)
must travel to the minimum or maximum position.
If response is wrong, refer to “Troubleshooting”
7. Switch power off.
8. Switch controller to normal operation (set switch no. 5
to
).
9. Switch power on. LED for the operating state must
light up (normal operation).
10. If used, activate auxiliary functions (setpoint change-
over, load-dependent switching contact, etc.).
11. If a remote setting unit is used, set the controller’s
temperature setting slider to EXT.
12. First, set temperature setting slider to the minimum
value, then to the maximum value: Observe the con-
trol. The response may neither be too fast nor too
slow.
If response is wrong, refer to “Troubleshoot-
ing”
13. Adjust the setpoint with the temperature setting slider.
14. Replace housing cover.
As a limiter
1. Switch on the temperature control.
2. Remove housing cover (limiter).
3. Lift flexible plastic cover so that you can access the
setting elements.
4. Choose operating action according to the following
table:
Controller: Limiter:
Operat-
ing mode
Switches
1 and 2
Limita-
tion
Operating
mode
Switches
1 and 2
Heating
Min. Heating
Heating
Max. Cooling
5. Make the following additional settings:
Control mode: P (switch no. 3 = , switch no. 4 =
)
Test mode: Switch no. 5 =
P-band Y1 on approx. 25 K
6. Replace housing cover.
7. Switch power on. LED for the operating state must
flash (test mode).
8. Check function depending on the type of limitation:
With minimum limita-
tion:
With maximum limitation
Set temperature setting
slider to the maximum
value:
Controller must increase
the temperature (heating
valve must open, cooling
valve must close)
Set temperature setting
slider to the minimum val-
ue:
Controller must reduce the
temperature (heating valve
must close, cooling valve
must open)
If response is wrong, refer to “Troubleshooting”
9. Switch power off.
10. Switch limiter to normal operation (set switch no. 5 to
)
11. Adjust the limit temperature.
12. Replace housing cover.
4


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RLE162 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RLE162 in the language / languages: English, German, Dutch, Danish, French, Italian, Polish, Swedish, Spanish as an attachment in your email.

The manual is 0,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info