620375
2
Zoom out
Zoom in
Previous page
1/2
Next page
CE1B3076.1en / 02.Jun 2010 Subject to change Siemens Building Technologies
Button lock
Press operating mode button
for 7 seconds to lock or unlock the buttons if
manual button lock is configured (parameter P14 = 2).
The thermostat automatically locks the buttons 30 seconds after the last
adjustment if "Auto lock" is configured (P14 = 1).
The key symbol
indicates locked buttons.
Reminder to clean filters
External faults
Commissioning (by qualifie
d HVAC installer)
To adapt the thermostat to your system and optimize the control performance, a number
of control parameters can be adjusted. This can also be made during operation without
opening the thermostat.
Control sequence
Recalibrating the sensor
Note: Economy mode
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for
cooling. Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is
inactive, i.e. no protective heating or cooling function. Risk of frost!
Control parameters
Proceed as follows to change the most important control parameters:
(Your HVAC installer can set additional parameters)
+ / -
+ / -
+ / -
+ / -
1. Set the thermostat to Protection
2. Press - and + simultaneously for a minimum of 3 seconds.
Release them and, within 2 seconds, press + again for 3 seconds. "P01" is displayed.
3. Repeatedly press the + or button to select the required parameter.
P01 P02 P08 P13
+-+
--
+
3057z03
P14
-
+
-
P12
+-
4. Press + and simultaneously, the current value of the selected parameter starts to flash, allowing you to change
the value by repeatedly pressing + or .
5. The next parameter is displayed when you press + and again simultaneously.
6. Repeat steps 3 to 5 to display and change additional parameters.
7. Press + or until "End" is displayed, and then press + and simultaneously to save the change and exit parameter
entry mode. 10 seconds after the last display or setting, all changes are saved and the thermostat will leave parame
t
entry mode.
Please record all changes you make! (All temperature settings can be made in increments of 0.5 K)
FIL
This message reminds you to clean the filter on your HVAC equipment.
It will appear after __________ "fan operating hours" and disappear when
the thermostat is set to Protection (
). This reminder must be configured by
your HVAC installer.
AL1
AL2
This alarm message tells you an external alarm has occurred:
AL1 : ______________________
AL2 : ______________________
The alarms are configured by your HVAC installer
The thermostat can be used in systems either for heating only or cooling
only, manually selection of heating or cooling, or automatic heating / cooling
changeover. Depending on the selected application, the relevant modes are
available and can be adjusted by commissioning parameter P01 if needed.
The factory setting for 2-pipe and single duct application is "Cooling only",
and for 4 pipe application "Heating and Cooling"
If the room temperature displayed by the thermo
stat does not agree with the
temperature effectively measured (after min 1 hour of operation), the tem-
perature sensor can be recalibrated. With parameter P05 the temperature can
be adjusted by + or – 0.5 °C up to a maximum of + / - 3 °C.
Para-
meter
Description
Factory setting Setting range
P01 Control sequence
2-pipe, Single duct: [0…3]
1 (Cooling only)
4-pipe:. [2…4]
4 (Heating & Cooling)
0 = Heating only
1 = Cooling only
2 = Manual H or C
3 = Auto Changeover
4 = Heating & cooling
P02 Mode selection by user via operating mode button 1 (Protection, Comfort) 1 = Protection, Comfort,
2 = Protection, Comfort,
Economy
P04 Selection of °C or °F °C °C or °F
P05 Sensor calibration 0.0 K – 3 ... +3 K
P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
1 = Setpoint
P07 Additional user information 0 (no display) 0 = no display
1 = Temp in °C / °F
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5 ... 40 °C
P11 Setpoint of heating in Economy mode (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Setpoint of cooling in Economy mode (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 Electric heater in cooling mode ON OFF = Disabled
ON = Enabled
P14
Button lock
(Press operating mode button for 7 seconds to lock or
unlock the buttons)
0 (Disabled) 0 = Disabled
1 = Auto lock
2 = Manual lock
2


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-rdf300

Reset search

  • i want change the user address ,so how can i can i change , can you give me idea how to change that Submitted on 7-1-2021 at 08:15

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF300 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF300 in the language / languages: English as an attachment in your email.

The manual is 0,32 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF300

Siemens RDF300 User Manual - German - 2 pages

Siemens RDF300 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info