CE1G2226X 02.02.2000 3/6
Commissioning
1. Remove controller from its baseplate
First open the cover and remove the time switch as shown
on Fig. A. After closing the cover, proceed as shown on
Fig. B and C.
2. Mount baseplate and check wiring
Proceed as shown on Fig. D. For correct wiring, refer to
"Connection diagrams".
Caution: 230 V!
3. Configuration
3.1 Set DIP switch for switching cycle
Self learning Adaptive control (standard):
For all normal situations.
PID 12 Normal controlled systems:
For situations with normal temperature
variations.
PID 6 Fast controlled systems:
For situations with great temperature
variations.
2-Pt Difficult controlled systems:
Proper on/off controller with a switching
differential of 0.5 °C (±0.25 °C).
3.2 Offset
10
15
20
25
30
5
(°C) (°C) Pos.
22.00 20.00 8
21.75 20.00 7
21.50 20.00 6
21.25 20.00 5
21.00 20.00 4
20.75 20.00 3
20.50 20.00 2
20.25 20.00 1
20.00 20.00 0
19.75 20.00 F
19.50 20.00 E
19.25 20.00 D
19.00 20.00 C
18.75 20.00 B
18.50 20.00 A
18.25 20.00 9
3.3 DIP switch reset
If one or several DIP switch positions or settings on the
offset potentiometer are changed, a reset
must
be made!
Otherwise the previous settings are still active!
4. Replacing the room temperature
controller
Proceed as shown on Fig. E and F. After that, the cover
can be opened and the time switch can be mounted.
5. Battery transit tab
As soon as the battery transit tab is removed, the unit
starts to operate.
6. Changing from 24-hour to weekly time
switch / Replacing time switch
If a change between a 24-hour time switch (AUZ3.1) and a
weekly time switch (AUZ3.7) is wanted or the time switch
has to be replaced, just proceed as shown in Fig. A. Before
that the cover must be opened.
7. Functional check
a) Open front cover. Move setting slider to .
b) Set the set value temperature to 30 °C by turning the
upper setting knob in plus direction.
c) The relay and thus the regulating unit must respond
after no more than 1 minute. If this is not the case:
Check regulating unit and wiring
Room temperature may be higher than 30 °C
d) Reset set value temperature
to its previous level
(20 °C).
e) Move setting slider to AUTO
.
8. Notes
If the reference room is equipped with thermostatic
radiator valves, they must be set to their fully open
position.
The local regulations and standards for electrical
installations must be observed.
The factory setting of all DIP switches is OFF.
Corrected DIP switch settings must be activated by
making a DIP switch reset.
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RAV12 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RAV12 in the language / languages: English, German, French, Italian as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RAV12

Siemens RAV12 User Manual - English - 2 pages

Siemens RAV12 User Manual - German - 2 pages

Siemens RAV12 User Manual - German - 8 pages

Siemens RAV12 User Manual - French - 2 pages

Siemens RAV12 User Manual - Italian - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info