Siemens AG Österreich, 05/2010 3/7 LOGO!Power 5V/6,3A, 12V/4,5A, 15V/4A, 24V/2,5A
ENGLISH
!
Warning notes
LOGO!Power is a stabilized power supply unit designed for use on the single-phase a.c. mains. The power supply unit must be
installed in compliance with the relevant DIN/VDE Regulations or the specific national standards. The connection to the supply
voltage must be performed in accordance with VDE 0100 and VDE 0160. A protective device (fuse) and a disconnecting switch for
safety isolation of the power supply unit must be provided. Trouble-free and safe operation of the unit is dependent on proper
transport and storage, as well as installation by qualified personnel.
Danger of electric shock !
During the operation of any electric devices, it is inevitable that certain parts of these devices are subject to hazardous voltages.
Improper use of these devices can therefore result in loss of life or severe personal injuries, as well as substantial property damage.
Potentiometer U
A is only allowed to be actuated using an insulated screwdriver!
Caution !
Electrostatically sensitive devices (ESD). Devices may only be opened by qualified personnel !
Installation and assembling:
LOGO!Power may only be installed and wired by a qualified expert who is conversant with and observes the generally applicable technical
standards and the relevant standards and specifications.
VDanger Before starting any installation or maintenance work, turn the main switch of the plant off and secure the unit against being re-
energized. An appropriate disconnecting switch must be provided for maintenance, in order to be able to disconnect the unit from the supply
circuit. LOGO!Power is a built-in device and must therefore be installed in a distributor box or a control cabinet. After installation, it must be
ensured that all the terminals are properly covered. Only then is the unit sufficiently protected against accidental touching of live parts.
The unit can be snapped onto DIN EN 50022-35x15 or DIN EN 50022-35x7,5 bars. To snap the unit on to the DIN bar, hang it with its nose a
into
the bar d and press until the spring s snaps into place (see page 4). If difficulty is experienced in snapping the unit on to the bar, loosen the
spring s
slightly as described under "Removing the Power Supply Unit". To remove from the DIN bar, use a screw driver to loosen the spring s in
the direction of the arrow.
Use a screw driver with a 3 mm blade for wiring (Terminal torque is 4,4Lb-in). No connector sleeves are required for the terminals. You can use
wires (use copper wire rated 65/75°C) up to a cross-section of 1 x 2,5 mm
2
(AWG 14) or 2 x 1,5 mm
2
(AWG 16). Under no circumstances may the
mains cable and the outgoing feeder be routed together! When using LOGO!Power together with devices subject to the class of protection I (with
PE conductor), a link „-“ to „PE” having a min. cross section of 1.5 mm
2
must be established.
To ensure proper heat dissipation, install the unit vertically with the input and output terminals on the top. Clearances of 2 cm should be provided
above and beneath the unit, in order not to restrict the natural convection.
Parallel connection of two similar devices to increase the power is permitted (provided the difference of the output voltages is < 0,2% and the line
impedances are equal to the load
).
It must be guaranteed that installations in EX applications are conducted according to protection class IP 54.
Technical specifications:
Specifications valid for input voltage 230 V AC and ambient temperature +25 °C, unless otherwise stated. They are
subject to change without prior notice.
Type: 5V/6,3A 12V/4,5A 15V/4A 24V/2,5A
Order-No.: 6EP1311-1SH12 6EP1322-1SH02 6EP1352-1SH02 6EP1332-1SH42
Input:
Rated voltage V
in: 100-240 V AC 100-240 V AC 100-240 V AC 100-240 V AC
Voltage range: 85...264 V AC 85...264 V AC 85...264 V AC 85...264 V AC
Line frequency range: 47...63 Hz 47...63 Hz 47...63 Hz 47...63 Hz
Mains buffering: > 40 ms > 40 ms > 40 ms > 40 ms
Rated current I
in: 0,71-0,37 A 1,13-0,61 A 1,24-0,68 A 1,22-0,66 A
Protection in the mains supply line: recommended: circuit breaker (IEC 898) up from 16 A char. B or up from 10 A char. C
Output:
Rated voltage V
out: 5 V DC 12 V DC 15 V DC 24 V DC
Residual ripple/spikes: < 100/100 mV
pp < 200/300 mVpp < 200/300 mVpp < 200/300 mVpp
Setting range: 4,6...5,4 V DC 10,5...16,1 V DC 10,5...16,1 V DC 22,2...26,4 V DC
Rated current I
out: 6,3 A 4,5 A 4 A 2,5 A
Current limitation : 8,2 A typ. 5,9 A typ. 5,0 A typ. 3,4 A typ.
Efficiency at full load: 83 % typ. 85 % typ. 85 % typ. 87 % typ.
Enviromental conditions:
Transportation and storage temperature: -40 °C...+70 °C -40 °C...+70 °C -40 °C...+70 °C -40 °C...+70 °C
Ambient temperature during operation: -20 °C...+55 °C -20 °C...+55 °C -20 °C...+55 °C -20 °C...+55 °C
Degree of protection: IP 20 IP 20 IP 20 IP 20
Pollution Degree enviroment: 2 2 2 2
Humidity rating: Climate category 3K3 acc. to EN 60721, relative air humidity 5...95 %, without condensation
EMC interference emission: EN 50081-1, class B acc. to EN 55022
EMC interference immunity: EN 61000-6-2, EN 61000-4-2/-3/-4/-5/-6/-11
Safety:
Protection class: Class II (without protective earth PE)
Galvanic isolation primary/secondary: SELV output voltage acc. to EN 60950 and EN 50178
Certificates:
CE CE marking acc. to 2004/108/EG and 2006/95/EG
UL UL 508 (Listed, File E197259), UL 60950 (Recognized, File E151273), NEC Class 2 for 6EP1332-1SH42
FM Class I, Division 2, Groups A,B,C,D, T4
GL Approval for shipbuilding to Germanischer Lloyd
ABS Approval for shipbuilding to American Bureau of Shipping for 6EP1322-1SH02 und 6EP1332-1SH42
ATEX ATEX94/9/EC Kat.3;Ex, nA IIC T3
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens LOGO Power at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens LOGO Power in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 0,32 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info