Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 17/20
47 Fan overrun time
3)
00.00...30.00 mm.ss 05.00 mm.ss
48 Min. heating circulator running time
11)
00.00...30.00 mm.ss 05.00 mm.ss
49 Heating circulator kick interval
10)
00.00...24.00 hh.mm/
Auto/Cont Auto
50 Alarm delay air flow start
12)
00.00...10.00 mm.ss 00.20 mm.ss
51 Alarm delay air flow operation
12)
00.00...10.00 mm.ss 00.10 mm.ss
52 Alarm delay AUX
12)
00.00...05.00 mm.ss 00.00 mm.ss
53 E7, E8 control input on time 4) 00.00...12.00 hh.mm 00.00 hh.mm
54 Startup time (damper fully closed)
5)
00.00...60.00 mm.ss 00.00 mm.ss
55 Preheating time 00.00...10.00 mm.ss 00.00 mm.ss
56 Power up start delay
13)
00.00...30.00 mm.ss 00.00 mm.ss
57 Setpoint 10...+30 °C 1 °C
58 P-Band 1...100 K 10 K
59 TN
2)
00.00...04.00 mm.ss 01.00 mm.ss
60 Switching value fan speed I 500...1800 ppm 700 ppm
61 Switching value fan speed II 500...1800 ppm 1200 ppm
62 Design value full occupancy 500...1800 ppm 1000 ppm
63 P-band 100...800 ppm 400 ppm
64 Hours run counter
9)
0...9999 x 10 h (Read value)
65 Operation lock
6)
OFF/On OFF
66 RWI software version
7)
"00.00" (Read value)
67 Communication address
8)
----,0...126 - - - -
1) Indicates whether input E7, E8 is open or closed (control signal «yes» or «no»)
2) Integral action time (T
n
) = 0 s means: P-control for the respective control sequence
Integral action time (T
n
) > 0 s means: PI-control for the respective control sequence
3) Only when the RWI65.02 is configured for an electric air heater battery.
During the overrun time, the fan runs at speed I. On completion of the selected overrun time, the fans will
be switched off and the outside air dampers closed
4) Period of time during which the plant - after arrival of a pulse (> 2 s) at E7 or E8 - shall operate.
When set to 0 min, the plant is switched on or off the moment the signal arrives at E7 and E8 (external
time switch) (only in Automatic mode and when the internal time switch has switched off or is permanently
deactivated)
5) Period of time during which the plant may operate with 100 % recirculated air (after plant startup)
6) If operating level 1 is locked (data point value = On), it is not possible to change any values for two
minutes after closing the front door (exception: summer-/wintertime changeover).
Enabling by reopening the front door
7) The display shows the actual program number (software version)
8) Must be set if the controller is equipped with a communication module. If no communication module is
used, the value set has no effect on the RWI 65.02
9) Counted are the number of fan operating hours.
The reading can be reset either to zero or to the former value. Proceed as follows:
1. Press function button 10 (line 10)
2. Press setting button «» if the meter shall be reset to zero, or setting button «+» if the meter
shall
be reset to the former value
3. To confirm the resetting, press function button 10 again.
10) Active only if coded for hot water heating coil!
00.00 ð Circulator kick interval is disabled
00.05 - 24.00 ð Circulator kick occurs for 30 s according to the selected interval time
Auto ð Circulator is activated for 30 s every 24 h, or runs continuously when the
outside temperature is < 5 °C; the minimum circulator running time (data
point 48) is maintained
Cont ð Circulator continuously on
11) The setting of a minimum running time avoids too frequent activation/deactivation of the circulator
12) To avoid unnecessary faulty alarms, the fault status signal can be delayed
13) After a power failure and subsequent power restoration, it may be necessary to bring the controller back
into operation with a certain delay. This is to make certain that after a power failure, all plant elements
connected to the same mains network will not be switched on at the same time (peak loads)
14) To protect the plant, the second fan speed is disabled at very low outside temperatures. In that case, only
the first fan speed will be enabled. To avoid unnecessary fan speed changes when outside temperatures
greatly vary, a hysteresis of 2 K is used
Time elements
HR anti-icing protection
Demand controlled ventilation
Miscellaneous
Explanations
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens AEROGYR RWI65.02 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens AEROGYR RWI65.02 in the language / languages: English as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens AEROGYR RWI65.02

Siemens AEROGYR RWI65.02 User Manual - German - 50 pages

Siemens AEROGYR RWI65.02 Usermanual and installation guide - Dutch - 73 pages

Siemens AEROGYR RWI65.02 User Manual - French - 22 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info