Air and moisture in the refrigerant system have
undesirable effects as indicated below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze
and block capillary tubing.
Water may lead to corrosion of parts in the
refrigeration system.
Therefore, the indoor unit and tubing between
the indoor and outdoor unit must be leak tested
and evacuated to remove any noncondensables
and moisture from the system.
Air purging with vacuum pump
Preparation
Check that each tube(both liquid and gas
side tubes) between the indoor and outdoor
units have been properly connected and all
wiring for the test run has been completed.
Remove the service valve caps from both
the gas and the liquid side on the outdoor
unit. Note that both the liquid and the gas
side service valves on the outdoor unit are
kept closed at this stage.
Pipe length and refrigerant amount:
Connective
pipe length
Less than 5m
More than 5m Liquid side: 6.35
(Pipe length-5M)x15g
Air purging
method
Use vacuum
pump.
Use vacuum
pump.
Additional amount of
refrigerant to be charged
AIR PURGING
Air purging
12
When relocate the unit to another place,
perform evacuation using vacuum pump.
Make sure the refrigerant added into the air
conditioner is liquid form in any case (Not
applicable to the units adopt freon R22 )
Open the valve stem until it hits against the
stopper. Do not try to open it further.
Securely tighten the valve stem cap with a
spanner or the like.
Valve stem cap tightening torque
(See Tightening torque table in previous page ).
Caution in handling the packed valve
Outdoor
unit
Indoor
unit
Refrigerant
Packed valve
Half union
Gas side
Liquid side
AC
D
B
Fig.24
Flare nut
Stopper
Cap
Valve body
Valve stem
Fig.25
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Midea MSX - X Type DC Inverter Wandmodel at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Midea MSX - X Type DC Inverter Wandmodel in the language / languages: English as an attachment in your email.

The manual is 4,5 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Midea MSX - X Type DC Inverter Wandmodel

Midea MSX - X Type DC Inverter Wandmodel User Manual - English - 16 pages

Midea MSX - X Type DC Inverter Wandmodel User Manual - Dutch - 13 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info