Master volt Inte rnation al B.V. P.O.Box 22947, NL-1100 D K Amsterdam, The Netherlands. Tel.: + 31-20-3422100 Email: info@mastervolt.com Web : www.mastervolt.com J uly 2004
NEDERLANDS
Productbeschrijving en toepassing
De Mastervolt Bat tery Watch schakelt de aangesloten belasting af bi j:
• Onderspanning: de accuspanning i s lager dan he t ingestelde ond erspanningniv eau (U-low.o ff). De
belasting wordt pas weer ingeschakel d zodra de acc uspanning hog er is dan het inschakelniv eau (U-
low.on). Door ee n schakelvertr aging (30 sec.) is de B attery Watch is ongevoelig voor kortstondige
spanningsvall en.
• Overspanning: d e accuspanning is hoger is dan 15, 5V / 31,0V ( U-high.off). De belasting wordt w eer
ingeschakeld zodr a de accuspanning l ager is 15,0V / 30, 0V (U-high. on).
De Battery Watch is uitsluitend g eschikt voor 12VD C en 24VDC inst allaties met een n egatieve massa.
Installatie
Overtuig uz elf ervan dat de uitg ang van de v oedingsbron spanni ngsloos is g edurende de
installatiewerkz aamheden. Zorg er tevens voor dat er geen g ebruikers z ijn aangesloten o p de
accugroepen ter voorkoming van onveilige situaties.
De Battery Watch kan warm w orden als gevolg van grote strome n. Installeer de Battery Watch daarom
op een goed gev entileerde pl aats, bij voor keur op een v lakke metalen ond ergrond, met de koelribben
verticaal geplaatst. Monteer de Battery Watch zo dicht mogelijk bij de accu, maar nooit dire ct boven
een accu i.v.m. mogelijke corrosie ve accudampen.
Aansluiten
Zie tekening (“i nstallation”) v oor de juiste w ijze van aanslui ten. Monteer de negatieve aansl uitingen v an
de accugroepen e n de voedingsbron o p een gemeenschap pelijk massapunt.
Monteer een schakel aar tussen de “sw itch”-aansluiting en de massa w anneer u de Batter y Watch als
hoofdschakelaar v oor de aangeslot en belasting wilt gebruiken.
Instellingen
De Battery Watch detecteert aut omatisch de nominale accus panning (12V of 24V).
Aan de bovenz ijde van de Batt ery Watch bevi ndt zich een DIP-sw itch voor het instellen van he t
onderspanningniveau. Gebruik een kleine sch roevendraaier om de instelling en te wijzigen. Zie tabel
“DIP-settings” voor instellingen.
Indien DIP-switches 1,2 en 3 tegelijkertijd op ‘ON’ staan ingeste ld, reageert de Battery Watch niet op
onderspanningen. U kunt het gel uidssignaal uitschakelen wann eer u DIP-sw itch 4 op ‘ON’ instelt.
Veiligheidsvoorschriften en –maatregelen
1. Installeer de Batter y Watch volg ens bovengenoemd e instructies
2. Gebruik de Battery Watch nooit op een locatie met gas- of stofontpl offingsgevaar.
3. Aansluitingen en beveiligingen moet en in overeenstemming met de plaatselijk geldende
voorschriften w orden uitgev oerd.
4. Gebruik kabels met voldoende dra addoorsnee en houd alle afstanden zo kort mogelijk. Gebru ik
deugdelijke kabelschoene n en draai alle aansluitmoeren g oed aan. (zie ‘nut instr uction’)
Garantiebepalingen
Mastervolt garandeert dat de Battery Watch is geproduceerd volg ens de wettelijk van toep assing
zijnde normen en bepaling en. Gedurende de productie en v oor afleveri ng zijn alle appar aten uitvoer ig
getest en gecontr oleerd. Wanneer niet volgens de in deze handlei ding geg even voorschriften,
aanwijzing en en bepalingen w ordt gehandeld , kunnen besc hadigingen o ntstaan en/of het apparaat z al
niet aan de speci ficaties v oldoen. Een en and er kan inhoude n dat de garanti e komt te verv allen.
De garantietermijn is t wee jaar.
Aansprakelijkheid
Mastervolt kan niet aansprakelijk w orden gesteld voor:
• Schade ontstaan do or het gebruik v an de Batter y Watch
• Eventuele fouten in bijbehor ende handlei ding en de gev olgen daarvan
• Ander gebruik g eldend als niet conform de be stemming van h et product
INSTALLATION
ENGLISH
Product description and applicati on
The Mastervolt Batter y Watch disconn ects its load in case o f:
• Under voltage: th e battery voltage is below the adjusted under voltage lev el (U-low.off). The load is
reconnected again w hen the batt ery vol tage is higher than t he switching l evel (U-low .on). Because of
a 30 seconds switching delay, the Battery Watch will not respond to short voltage dips.
• Over voltag e: the battery v oltage is above 15. 5V / 31.0V (U-hi gh.off). The load i s reconnect ed again
when the batter y voltag e is below 15.0V / 30.0V (U-hig h.on).
The Battery Watch can only be a pplied in 12V DC and 24VDC inst allations with a negative com mon
ground
Installation
Be sure that the output of the s upplying source is sw itched off duri ng installation. Als o be sure that n o
consumers are connec ted to the batt eries during instal lation, to prevent hazardous situati ons.
Install the Batter y Watch not onl y as close as possible to the supply ing source, but to the batteries as
well, but do not install The Battery Watch straight abov e the batteri es because of possible corrosive
sulphur fumes. The battery is olator must be in stalled in a w ell-ventilated environment, as high currents
will heat up the battery isolator . Preferably , the Battery Watch should be mounted on a fl at metal
surface with the fins vertical
Connections
For correct connecti on - see drawing “installation”. Con nect the negat ive poles of the ba ttery sets and
the supplying source to a common g round.
Connect a switch b etween the “ switch”-connecti on and the common ground if you w ant to use the
Battery Watch as a main switch for the connected load.
Adjus tme nts
The Battery Watch automatical ly detects the nominal batt ery voltage ( 12V or 24V).
On top of the Batter y Watch a DIP-sw itch is situated to adjust the u nder voltage level. Re fer to the
“DIP-settings” tabl e for adjustme nts.
If DIP-switches 1, 2 and 3 are sw itched ‘ON’ together , the Battery Watch does not r espond to under
voltages. If DIP-switch 4 is sw itched ‘ON’, the audible alar m is switched off.
Safety regulations and measu res
1. Install the Battery Watch according to the stated ins tructions.
2. Never use the Battery Watch at a loc ation where ther e is danger of gas or dust ex plosions.
3. Connections and safet y features must be executed accordi ng to the local ly applicable reg ulations.
4. Use cables with appro priate size w ire and keep the cabl e connections as s hort as possible. U se
reliable terminals and fasten th e bolts tightly , but do not over torque (also see ‘ nut instructio n’).
Guarantee terms
Mastervolt guarante es that the Ba ttery Watch has b een built accordi ng to the legally applicable
standards and sti pulations. During production and before deliv ery all units w ere exhaustiv ely tested
and controlled. I f you fail to ac t in accordance w ith the regulations, in structions and stipul ations of this
user’s manual, damage ca n occur and/or the unit will not fulfil the specification s. This may mean that
the guarantee will becom e null and void.
The guarantee period is 2 y ears.
Liability
Mastervolt cannot b e held liable for:
• Damage resulting fro m the use of the Battery Watch.
• Possible errors i n the included manual and th e consequences of th ese.
• Use that is inconsistent w ith the purpose of th e product.
BATTERY WATCH
SPECIFICAT IONS
Article number 83 20 0150
Input Voltage 8 – 32V
Switch OFF under v oltage (U-low .off) 9.0V…12.0V or 18. 0V…24.0V (adj ustable by DIP-setting s)
Switch ON under v oltage (U-l ow.on) 10.5V…13.0V or 2 1.0V…26.0V (adjusta ble by DIP-setti ngs)
Switch OFF over v oltage (U-high.off) 15.5V or 31.0V ( fixed)
Switch ON over voltage (U-hi gh.on) 15.0V or 30.0V ( fixed)
Delay high v oltage OFF 1 sec.
Delay high v oltage ON 10 sec.
Delay low voltage OFF 30 sec.
Delay low voltage ON 10 sec.
Nominal Cur rent 100A
Maximum Curre nt (P30) 150A
Voltage drop <0.2V
Remote main sw itch (optional) Single pole, on-o ff contact (sw itching current: 1mA)
DIP SETTINGS
0 Audible alarm (buzz er) = ON
1 Audible al arm (buzz er) = OFF
Ç
1 ON
0 OFF
1 2 3 4 U-bat = 12V U-bat = 24V
È È È U-low.off U-lo w.on U-low.off U-low.on
0 0 0 9.0V 10.5 V 18.0V 21.0V
1 0 0 9.5V 11.0 V 19.0V 22.0V
0 1 0 10.0V 11.5V 20.0V 23.0V
1 1 0 10.5V 12.0V 21.0V 24.0V
0 0 1 11.0V 12.5V 22.0V 25.0V
1 0 1 11.5V 13.0V 23.0V 26.0V
0 1 1 12.0V 13.0V 24.0V 26.0V
1 1 1 OFF OFF OFF OFF
LED INDICATIONS RECOMMENDED WIRE SIZES
LED # DC-Current Wire size (up to 3 meters)
50-75 Amp 25 mm² (AWG 3)
75-100 Amp 35 mm² (A WG 1-2)
100-150 Amp 50 mm² (AWG 0)
1
2
3
4
Power
High battery
Low battery
Overload
LED: 1 2 3 4
On Over voltag e Under voltage Overload
Aan Overspanning Onderspanning Overbelasting
Ein Überspannung Unterspannung Überladung
Marche Sur-tension Sous-tensio n Surcharge
On Sov ratensione Bassa tensione Sovraccarico
On Sobr etensión Subtensión Sobrec arga
+ –
Battery Accu
Akku Batter ie
Batteria Batterí a
Battery charg er
Acculader
Akkulader
Chargeur
Caricabatterie
Cargador
+
Load
Belasting
Last
Charge
Carico
Carga
Off
Uit
Aus
Arrêt
On
Aan
Ein
Marche
Ø 0,5 mm²
157 mm
140 mm
140 mm
70 mm
+
–
1 2 3 4
Remote main switch
Bediening als hoo fdschakelaar
Fernbedienung H auptschalter
Télécommande d’ interrupteur principal
Commando interr uttore per car ico remoto
Remoto desconact ador de batterí a