CO2 CONTROL - assembly and operating instructions
-19-
Alarm mode
Display
Measure
Pre-alarm
Intermittent
warning sound, red
warning light
flashes
Only enter the hazard area if a second person is
present adjacent to the hazard area. Open all doors
wide open!
1. Shut off all of the gas bottles.
2. Find and fix the leak and/or fault.
Call in the dispensing system service team if
necessary!
3. When the CO
2
content drops below the threshold
value, the alarm will reset automatically.
Fault
Continuous
warning sound,
yellow warning
light lit
These can include:
1. Cable break → The cable must be replaced
2. Device fault → Replace the component
3. Sensor unit fault → Replace the sensor unit
4. When replacing the sensor unit with no
re-initialisation → Initialise the system
5. Heavy smoke → Eliminate the cause; the system
will return to operating mode by itself
6. Severe sudden temperature variations → After a
short time, the system will return to normal
operating mode
Pressing the ALARM OFF key will restart the gas
detection system. If the system fault reoccurs, the
equipment will need to be repaired by the service
team.
7 Warranty
KUNDOxT provides a warranty for technical defects arising from the manufacture of the gas detection system within 24 months following the date of assembly
and commissioning.
The warranty covers the replacement or repair of the device free of charge. Additional costs incurred thereby are not covered.
The warranty is only valid when the card attached to the device is retained by the equipment operator, and the attached postcard has been completed by the
installation service and returned by the owner.
Please ensure that the serial number of the installed device is entered on the postcard.
KUNDOxT guarantees that the system requires no calibration and/or adjustments within 4 full years of operation. After 4 years of operation, a calibration will be
performed at our plant at cost (see 4. Maintenance).
8 Instructions for the prevention of hazards due to CO
2
gas
8.1 Code of conduct
1. Keep calm!
2. Acknowledge the audible alarm by pressing the "ALARM OFF" key on the warning unit, and another alarm off switch on the AM / AM PLUS version.
3. Determine which alarm is involved!
Main alarm: Continuous sound, Red light lit
Pre-alarm: Intermittent warning sound Red light flashes
Malfunction: Intermittent warning sound Yellow light flashes
For the CO2 CONTROL AM / AM PLUS versions in a CO
2
refrigeration equipment area, please observe the notes in the CO2 CONTROL AM / AM PLUS installation
sheet!
When the main alarm is triggered, no further access to the hazard area must be allowed!
To eliminate the hazard, an extraction unit (where available) must be used, or the local
fire brigade must be called.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kundo xT CO2 Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kundo xT CO2 Control in the language / languages: English as an attachment in your email.

The manual is 1,55 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kundo xT CO2 Control

Kundo xT CO2 Control Usermanual and installation guide - German - 54 pages

Kundo xT CO2 Control Usermanual and installation guide - German - 53 pages

Kundo xT CO2 Control Usermanual and installation guide - Dutch - 52 pages

Kundo xT CO2 Control Usermanual and installation guide - French - 20 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info