554869
1
Zoom out
Zoom in
The SD-282ST combined smoke and heat detector MLW51102 1
The SD-282ST combined smoke and heat detector
The SD-282ST is used to detect fire hazards in the interior of residential or commercial
buildings. It is not designed to be installed in industrial premises.
The detector indicates fire hazards using the built-in LED indicator and alarm outputs
ALARM and TAMPER. These outputs must be connected to control panels
complaining with EN 50131-3..
The SD-282 ST consists of two independent detectors – an optical smoke detector and
a heat detector. The optical smoke detector works on the principle of scattered light and
is very sensitive to large dust particles which are present in dense smoke. It is less
sensitive to smaller particles generated by the combustion of liquids such as alcohol.
That is why there is also a built-in heat detector which has slower reaction but is much
better at detecting fire which generates heat quickly with a small amount of smoke. The
microprocessor performs digital analysis of these values which markedly increases false
alarm immunity.
Detector range
The smoke detector must be installed so that any smoke easily drifts into the detector,
e.g on the ceiling. It is suitable for residential buildings but not suitable for free spaces,
outdoor environments or interiors with extremely high ceilings (above 5 m) where fire by-
products can disperse over a large area – the smoke would not reach the detector
position.
The detector must always be placed in the section leading to the exit of the building
(escape route), see Figure 1. If the building has a floor area greater than 150 m
2
,
installation of an additional detector in some other suitable place is required, see Fig.2.
1
2
33
4
Fig. 1
2
1
3
3
4
3
Fig. 2
1-kitchen
2-living room
3-bedroom
4-children’s bedroom
- Basic security
- For more security
1
3
3
3
Fig. 3
For large buildings it is recommended to place additional detectors in rooms where
people sleep and in rooms with an increased risk of fire - see Fig.3.
Installation on level ceilings
Place the detector in the centre of the room if possible. The detector must not be
recessed into the ceiling due to the possible existence of a cool air layer on the ceiling.
Never place the detector in the corner of the room though (always keep at least a 0.5
m distance from the corner) see Fig 4.
Installation on sloping ceilings
If the ceiling is not suitable for mounting on a level surface (e.g. a room under a roof ridge),
the detector can be installed as in Fig. 5.
0.5m
TOP
Fig. 4
0,9 m
Fig. 5
centre of the room, best location
acceptable location
Walls, partitions, barriers and lattice ceilings
The SD-282ST detector must not be installed closer than 0.5 m from any wall or
partition. A narrow room with a width of less than 1.2m requires the detector(s) to be
placed at a distance of at least one third of the room’s width away. In the case of separating
walls (partitions, warehouse objects) which do not reach the ceiling, the space is
considered to be fully separated if the gap between the top of the separating wall and
the ceiling does not exceed 0.3 m. A free space of at least 0.5m is required under the
detector. Any irregularities of the ceiling (e.g. girders) exceeding 5 % of the ceiling height
shall be considered a wall and the above mentioned limitations shall apply.
Ventilation and air circulation
The detectors must not be installed directly by a fresh air inlet (e.g. air
conditioning vents). In the case of air being supplied through a perforated ceiling, each
detector must be placed so that no perforation hole occurs within 0.6m of the detector.
Avoid installing the detector in the following locations:
places with poor air circulation (niches, corners, apexes of A-shaped roofs, etc.)
places exposed to dust, cigarette smoke or steam
places with over-intense air circulation (close to ventilators, heat sources, air
conditioning outlets, etc.)
in kitchens and other cooking places (because steam, smoke or oily fumes can reduce
detector sensitivity).
beside fluorescent lights (electrical interference can cause a false alarm)
in areas with lots of small insects
Please note: Most false alarms are caused by improper
detector location.
See CEN/TS 54-14 standards for detailed installation guidelines.
Installing the detector
Fig. 6: 1– detector cover opening; 2 – detector cover closing; 3 – optical
status signalling; 4 – arrow showing where to insert the detector; 5 –
configuration jumpers; 6 – connection terminals;
1. open the detector cover, by turning it anti-clockwise
2. attach the removed plastic base to the desired place with screws (not shown above).
3. set the required detector function – see the table below
ON NO contact 3 OFF
1
OFF NC contact 4 OFF
smoke (EN 54-7) or
heat (EN 54-5)
ON memory ON 3 ON
2
OFF memory OFF 4 OFF
smoke only (EN 54-7)
(not heat)
3 OFF
4 ON
heat only (EN 54-5)
(not smoke)
3 ON
4 ON
Both smoke and heat
(both conditions at the
same time)
4. connect ALARM and TMP terminals – first study the control panel installation manual
before connecting wires to the detector terminal board
TMP- has only NC function
5. connect power supply to the 12V terminals
6. close the module cover. The detector can be inserted in the plastic base in one position
only. The correct position is marked with arrows on both plastic parts.
Fire alarm
Optical detector: When smoke penetrates into the detector, the detector starts
flashing red.
Heat detector: When the temperature reaches the set limits, the detector starts
flashing red.
Alarm memory: If it is enabled, alarm indication continues even when the smoke clears
or when the temperature decreases. The indication is terminated by disconnecting power
supply or by turning the detector anti-clockwise (tamper sensor activation).
Fault indication
The detector checks its functioning. If any faults are discovered, it starts flashing
rapidly for about 2 minutes. Then there are 3 short flashes every 30 seconds.
In such a case, disconnect the power supply for 1 minute and then reconnect it. If the
LED indicator starts flashing again after 1 minute, send the detector to a service centre.
Technical specifications
Power 9 - 15V DC / 5 mA
Smoke detection optical light scattering
Smoke detector sensitivity m = 0.11 - 0.13 dB/m pursuant to EN 54-7
Heat detection class A2 according to EN 54-5
Alarm temperature + 60°C to + 70°C
Operating temperature range -10 to +80°C
Dimensions, weight diameter 126 mm, height 52 mm, 150 g
Conformity EN 54-7, EN 54-5, EN 50130-4, EN 55022
1923-CPD-0244
JABLOTRON ALARMS a.s. hereby declares that the SD-282ST detector is in
compliance with the essential requirements and other relevant provisions of
Directive 1989/106/EC and 2004/108/EC. The original of the conformity
assessment can be found at www.jablotron.com, Technical Support section.
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer or
directly to the producer after use. For more information visit
www.jablotron.com.


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Jablotron SD-282ST at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Jablotron SD-282ST in the language / languages: English as an attachment in your email.

The manual is 0,11 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info