JA-82K control panel installation manual - 7 - MKH51103
Enter the appropriate programming sequences – see the following
description (an unfinished sequence can be escaped from by pressing
the # key).
To exit Service Mode press the # key.
6.1 Exit delay time
An exit delay time occurs while setting (arming) the system. During this
time period delayed or next-delayed detectors can be triggered without an
alarm occurring. To program the delay time, enter:
2 0 x
where x is a number from 1 to 9 determining the duration in
steps of tens of seconds (1=10 s, 2=20 s,....)
If there is a final-door detector in the system then the exit delay is
multiplied by 30 s instead (1=30 s, 2=60 s,...).
Example: To program a 20 seconds exit delay, use the sequence 202 (if
there is a final-door detector, a 60 seconds delay will result).
Factory default setting: x = 3
6.2 Entrance delay time
The entrance delay time is provided to unset (disarm) the system after a
first delayed detector has been triggered. To program this time, enter:
2 1 x
where x is a number from 1 to 9 determining the delay in
multiples of 5 seconds (1=5 s, 2=10 s,....)
If the entrance delay is triggered by a final-door detector, then parameter
x is multiplied by 30 s instead. (1=30 s, 2=60 s,...) – in this case it means that
the entrance delay would be six times longer than if it had been triggered by
an ordinary detector.
Example: To program a 20 seconds entrance delay, enter the sequence 214
(if the delay has been activated by a final-door detector, a 120 seconds delay
will result instead).
Factory default setting: x = 4
6.3 Alarm duration time
This parameter limits the duration of a triggered alarm. After the alarm
state expires, the control panel will return to its previous state, i.e. as before
the alarm occurred. The alarm state can also be terminated by an authorised
user. To program the alarm duration enter:
2 2 x
where x is a number from 0 to 9 determining the alarm duration:
0 = 10 s, 1 = 1 min., 2 = 2 min. up to 8 = 8 min., 9 = 15
min.
Note: There can be up to 5 different alarms in the system: intruder, tamper,
fire, panic, and technical alarm.
Example: Alarm duration of 5 min. = sequence 225
Factory default setting: 4 minutes
6.4 PGX and PGY functions
The functions of PGX and PGY can be programmed by entering
sequences:
2 3 x for PGX
2 4 x for PGY
where x determines the PG function or the event which triggers a
change of PG state:
x Unsplit system Split system
0
Completely (ABC) set
= PG on
Alarm A = PG on
1
Anything set = PG on Alarm B = PG on
2
AB set (not ABC) = PG on Entrance delay A = PG on
3
Fire alarm = PG on Entrance delay B = PG on
4
Panic = PG on A set = PGX on, B set = PGY on
5
Any alarm = PG on
(excluding Panic)
Panic A = PGX on
Panic B = PGY on
6
AC dropout = PG on Fire = PGX on, dropout =PGY on
7*
ON/OFF
8*
2 seconds pulse
fig. 9 PG outputs settings
* The ON / OFF and 2 second pulse functions can be controlled from
the keypad by keying in * 8, *9 or using the arrow keys ON and #OFF
see 6.26) or they can be operated by a code or card. These PG output
functions can also be controlled by signals from keyfobs or detectors (see
6.40).
Notes:
The PGX and PGY outputs are not only provided as control panel
terminals, but the signals are also wirelessly transmitted for UC and AC
modules.
The status of PGX and PGY outputs can be displayed by pressing the
“?” key. The names of the outputs can be edited – see 6.47.
Example (for unsplit systems): Assigning an ON/OFF function to the PGX
output = sequence 237. Assigning a panic function to the PGY output =
sequence 244.
Factory default setting: PgX= ON/OFF, PgY= anything set
6.5 Changing telephone numbers in maintenance
mode
If the control panel is equipped with a JA-8xY, JA-80V or JA-80X
communicator, then this sequence enables the holder of the master code
(system administrator) to program telephone numbers for alarm reporting in
maintenance mode. Programming telephone numbers is the same as in
Service mode (see communicator manual):
2 5 1 programming enabled
2 5 0 programming disabled
Factory default setting: programming disabled.
6.6 Radio interference indication
The control panel is capable of detecting and indicating radio
communication jamming. If this function is enabled, any radio jamming longer
than 30 s will trigger fault indication and if armed the alarm is triggered.
2 6 1 enabled
2 6 0 disabled
Factory default setting: disabled.
Note: In some places the system can be permanently or occasionally
affected by radio interference, e.g. by nearby radar stations, TV transmitters
etc. In most cases the system can tolerate such effects, but with this anti-
jamming function disabled.
6.7 Radio communications supervision
If enabled, the control panel can routinely check the wireless
communication of its devices. If communication with a particular device is lost
for two hours, the control panel can report a fault indication.
2 7 1 indication enabled
2 7 0 indication disabled
Notes:
In the OASiS system, communication is checked every 9 mins.
In detectors used for car protection, (JA-85P, JA-85B) it is possible to
disable radio communication supervision. It allows car detectors to be
excluded from supervision to avoid alarm triggering when driving the
car away from the system.
Random dropouts in communication can occur in some installations
near e.g. airports or TV towers. The system is still reliable in such
situations as high-priority transmissions are repeated often. We
recommend disabling communications supervision in cases like this.
Factory default setting: supervision disabled.
6.8 RESET enabled
If resetting is enabled, it is possible to return the control panel to its
original factory-default settings via the reset link on the main board. (see
section 3.8).
2 8 1 RESET enabled
2 8 0 RESET disabled
Warning: If resetting is disabled and the service code has been forgotten, it
would no longer be possible to enter Service mode. If this happens, send the
control panel back to the manufacturer.
Factory default setting: RESET enabled.
6.9 Enrollment to a sub control panel for setting
control
If the control panel has another OASiS control panel enrolled as a sub-
system, then the sub-system reports all alarms, tampering and faults to the
master control panel. The master control panel reacts to particular signals
accordingly, and displays the sub control panel’s address as the source.
After sub control panel enrollment to the master control panel, these two
panels are independent concerning setting control. Each panel can be
operated by its own keypads or key fobs. If there is an alarm or fault in the
sub control panel, it is also indicated on the master control panel. In this
configuration it is impossible to control the sub control panel from the master
control panel.
If it is desired to control a sub control panel from a master control panel
(i.e. setting/unsetting), it is possible to enroll a JA-8x OASiS master control
panel to a sub control panel as a remote control as follows:
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Jablotron JA-82K OASIS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Jablotron JA-82K OASIS in the language / languages: English as an attachment in your email.

The manual is 0,66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Jablotron JA-82K OASIS

Jablotron JA-82K OASIS User Manual - English - 23 pages

Jablotron JA-82K OASIS Additional guide - English - 1 pages

Jablotron JA-82K OASIS Installation Guide - German - 23 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info