The GS-130 detects all mixtures of air and combustible gas (Natural Gas, Me-
thane, Propane, Butane, GPL, etc). The detector detects two levels of gas con-
centration - different output reactions.
The main GS-130 features are: high reliability and sensitivity, compact size,
230V (110V optional) power supply and long stability & lifetime.
Installation
A professional installer should install the
detector. (recommended in compliance
with EN 50244).
Fix the detector on the
wall. For gases lighter than
air (natural gas, city gas etc.)
install it close to the ceiling
(max. 15 cm under it) or
directly on the ceiling and on
the place expected to have
gas leakage. For gases
heavier than air (propane,
butane, etc.) install it close to
the floor or on the lowest
place of the room. The
detector should not be
located close to any obsta-
cles preventing natural air
circulation.
Memory
The memory function is disabled by factory default (when the concentration of
the gas drops down to normal, the GS-130 will stop the alarm signal).
Close the MEM jumperto select the memory function. Then the alarm indica-
tion, if triggered, will not stop unless the GS-130 power supply is terminated for a
while.
Power supply
Connect the power cord to the terminals marked 230V AC (or 110VAC). The
power inlet should be fused with an external fuse (max. 10A).
Outputrelay function
There is a dry relay contact available on the GS-130 output terminals:
•C - common contact
•NO- normally open contact
•NC- normally closed contact
This relay output can be used for an automatic gas-valve closer, alarm system
triggering or for other warning systems.
When the automatic gas-blocking function is used, the application of this shall
be according to national regulations and EN1775.
If the REL jumper is open, the relay will be triggered after the 1st level of gas
concentration is detected. If the REL jumper is closed, the relay will be triggered
after the 2nd level of gas concentration is detected.
green LED
red LED
NO230V
JABLOTRON
GS-130
REL
AUX
MEM
CACNC
buzzersensor
Fig. 2
red LED
Function
After switching the power on, the green LED willflash for 60 sec. (the detector
warms up). When the green indicator lights permanently the detector is ready.
If the gas concentration reaches the 1st level, short beeps will sound and red
LED I will go off.
If the gas concentration reaches the 2nd level,long beeps will sound and red
LED II will go off.
The output relay reacts depending on the REL jumper setting.
Warning -in the case of a gas alarm stay calm and act as follows: -do not
operate any switches
-do not use any kind of phone in the location of the gas leakage
-open any windows
-stop the gas leakage if possible or leave the place and call the gas
supply company
Warning – leaking gas can be smelled before the detector detects an
alarm-level concentration of gas. In this case, the cause of the gas
leak should be eliminated immediately.
Maintenance and testing
Keep the detector clean, it is important that its grids should not be blocked with
dust.
Use a gas cigarette lighter without the flame lit, to test the gas detector’s reac-
tion. Thedetector will react within 15 seconds.
Professional recalibration of the detector should be done at least once a
year. Contact your distributor for more details.
LED indicators
Green
•OFF
•Flashes
•ON
The detector is off
Warming up
Ready for gas alarms
Red I.
•ON
1
st
level of the gas concentration
Red II.
•ON
2
nd
level of the gas concentration
Red II.
Green
•Alternating
flashes
Error in the sensor
Specification:
Sensitivity (gas concentration):
Methane
Propane
Level 1
10
±
3% LEL (0.50% vol.conc.)
18
±
3% LEL(0.30% vol. conc.)
Level 2
18
±
3% LEL (0.80% vol. conc.)
30
±
3% LEL (0.50% vol. conc.)
Iso-butane
Level 1
23
±
3% LEL(0.30% vol. conc.)
Level 2
40
±
3% LEL (0.50% vol. conc.)
LEL = Lower Explosive Limit (100 %) according to EN 60079-20-1: for
methane 4,4 % vol. conc., for prophane 1,7 % vol. conc., for iso-buthane
1,3 % vol. conc., calibrated by iso-butane
Power supply230V(-15% to+10%) / 50Hz, 2 W, protection class II
Detection methodhot platinum filament
Buzzer sound level94dB/0.3m
Relay outputoptional for 1st or 2nd level, max. 230V AC/5A
Alarm memoryselectable
Response time20 s
Warm up timeapproximately 90 s
Working environment indoor use, -10 to +40°C, IP30
Working humiditymax 80 %
designed to operate at normal atmospheric pressure86 to 106kPa
Complies with EN 50194-1, EN 60079-29-1, EN 50130-4,
EN 55022, EN 60950-1
For non-explosive areas. Zone 2 according to EN 60079-10.
Certified by VVUÚ corp., certificated body No. 3076, by FTZÚ corp., certifi-
cated body No. 3051
Complies with the essential requirements of: 2006/95/ECLow
VoltageDirective- Health and safety protection, 2004/108/EC
EMC Directiveconcerningelectromagnetic compatibility and
2011/65/EU RoHSwhen used for its intended purpose.The
original of the conformity assessment can be found at
www.jablotron.com, Technical Support section.
Note: Although this product does not contain any harmful materi-
als we suggest you return the product to the dealer or directly to
the producer after use.
ready
green
red
1st level
2nd level
Fig. 1
OK
I.
II.
red
Gas Leak Detector GS-130 2/2 MEF51016
Need help? Post your question in this forum.
Report abuse
Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.
Product:
Forumrules
To achieve meaningful questions, we apply the following rules:
First, read the manual;
Check if your question has been asked previously;
Try to ask your question as clearly as possible;
Did you already try to solve the problem? Please mention this;
Is your problem solved by a visitor then let him/her know in this forum;
To give a response to a question or answer, do not use this form but click on the button 'reply to this question';
Your question will be posted here and emailed to our subscribers. Therefore, avoid filling in personal details.
Register
Register getting emails for Jablotron GS-130 at:
new questions and answers
new manuals
You will receive an email to register for one or both of the options.
Get your user manual by e-mail
Enter your email address to receive the manual of Jablotron GS-130 in the language / languages: English as an attachment in your email.
The manual is 0,34 mb in size.
You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.
The manual is sent by email. Check your email
If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.
The email address you have provided is not correct.
Please check the email address and correct it.
Your question is posted on this page
Would you like to receive an email when new answers and questions are posted? Please enter your email address.