T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
11 69-1510-4
TROUBLESHOOTING GUIDE
Table 6. Troubleshooting Guide.
Symptom Possible Cause Action
Display will not
come on.
Thermostat is not being
powered.
• Check if batteries are present and installed correctly.
— If batteries are present and installed correctly, replace
thermostat.
Temperature
display is incorrect.
Room temperature display has
been reconfigured.
Enter Installer Setup number 37 and reconfigure the display.
Thermostat is configured for °F
or °C display.
Enter Installer Setup number 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat.
Temperature
settings will not
change. (Example:
Cannot set the
heating higher or
the cooling lower.)
The upper or lower temperature
limits were reached.
Check the temperature setpoint:
• Heating limits are 4.5 to 32°C
• Cooling limits are 7 to 37°C
The setpoint temperature range
stops were configured.
Check Installer Setup numbers 34 and 35 and reconfigure the
setpoint stops.
Heating will not
come on.
No power to the thermostat. • Check for 24 Vac between R and W terminals (check for
750 mV on PowerPile
®
Systems).
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit
breaker.
— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in
the Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any
loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is
activated.
Wait up to five minutes for the system to respond.
System selection is not set to
Heat.
Set system selection to Heat.
Heating setpoint is below room
temperature.
Check heating setpoint. Set heating setpoint to desired
temperature.
Cooling will not
come on.
No power to the thermostat. Check for 24 Vac between R or RC and Y terminals
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit
breaker.
— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in
the Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any
loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is
activated.
• Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off
time (if required).
System selection is not set to
Cool.
Set system selection to Cool.
Cool setpoint is above room
temperature.
Check cooling setpoint. Set cooling setpoint to desired
temperature.
Heating or cooling
come on
momentarily and
shut off.
Heat or cool circuit is opening
up or becoming high
impedance.
Add resistor in parallel with load or install interface relay.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Honeywell T8602D Chronotherm IV at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Honeywell T8602D Chronotherm IV in the language / languages: English as an attachment in your email.

The manual is 0,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info