18. These models are supplied with a factory pre-set programme which will
be active after a RESET has been performed. The pre-s e t
programme is shown in the chart with the Setting Instructions.
The chart also has spaces for users own times and temperatures a s
required by them.
19. The time and programme memory are maintained by the batteries
which should last more than two years. Every 24 months the batteries
should be renewed. Internal circuitry retains the time and programme
memory for one minute, long enough for the batteries to be changed.
If the batteries volts drop, before a change is due, a battery symbol will
blink in the display. When this occurs the TP75-RF will operate
normally for 2 weeks. After the 15th midnight all relays will switch to
OFF, the unit will shut down with just the time shown. When new
batteries are fitted the unit will start to operate normally again.
Advise the User to enter their own times and temperatures in the chart on the
Setting Instructions.
Post-commissioning
Optimum Start Control
If this has been enabled, initially set to the recommended 30 minutes start-
up duration and the event 1 temperature is not achieved by the event 1 time,
then refer to the Setting Instructions and increase the start-up duration one
stage, i.e. to 1 hour.
If the space temperature at the beginning of an Optimum Start sequence is
consistently lower than the programmed event 1 temperature by more that
2°F, then the event 1 temperature may not be achieved by the event 1 time.
In this case the event 1 time should be brought forward sufficiently to
compensate, so that the comfort temperature is achieved when actually
required.
Intelligent Anticipator
If, when the heating equipment is switched on, the room temperature is 4°F
or more lower than the programmed temperature the electronic anticipation
function measures the rate of rise in the sensed temperature and will switch
the heating plant off before the programmed temperature is reached. The
residual heat in the system after the heating plant has shut down will ensure
that the comfort temperature is achieved. This will improve the comfort
conditions and minimise fuel consumption.
Commissioning
12. Lower the front flap and remove the anti-discharge paper strip from
between the batteries and their contacts, and ensure the mains power
to the control circuit is switched on.
13. Press and release the recessed RESET button to ensure the factory
pre-set programme is active.
14. Once the programming has been completed, communication between
the thermostat and the receiver module has to be established.
a) SINGLE ZONE SYSTEM WITH RX1 RECEIVER
1 - Press and hold the LEARN button of the TP75-RF for at least 3
seconds. The thermostat will now transmit a continuous signal which
contains its unique identity for a period of 5 minutes.
2 - Within the 5 minute period go to the RX1 receiver module and
press both "PROG" and "CH1" buttons together and hold for at
least 3 seconds, then release.
During this process the RX1 receiver will have learnt the unique
transmission code of the thermostat and will in future react to all
transmissions from that thermostat.
To stop the continuous transmission on the TP75-RF unit press the
s button.
b) TWO ZONE SYSTEM WITH RX2 RECEIVER
1 - Repeat as above for zone one (CH1).
2 - Repeat steps one and two above for zone two, remembering to
press "PROG" and "CH2" on the RX2 receiver.
c) THREE ZONE SYSTEM WITH RX3 RECEIVER
1 - Repeat as above for zones 1 and 2 (CH1 and CH2).
2 - Repeat as above for zone 3, remembering to press "PROG" and "CH3"
on the RX3 receiver.
15. Establish with the customer the requirements for the operating
mode, and adjust as follows:
Clock type - 24 hour or 12 hour with AM/PM indication.
The factory pre-set is 24 hour. To convert to 12 hour, press and
hold down the NEXT and DAY buttons until the display changes,
then release. (Repeat to return to a 24 hour clock.)
Temperature display - °C or °F
The factory pre-set is °C. To convert to display all temperatures i n
°F, press and hold down the DAY and COPY buttons until the
display changes. (Repeat to return to a °C display.)
16. Check the existing space temperature by pressing and holding
down the two buttons: NEXT and COPY, until the display changes from
time to temperature.
17a. If the set temperature is below the space temperature, use the
button to raise the set temperature. The flame symbol will appear in the
display. Check that the heating plant operates correctly.
17b. If the set temperature is above the space temperature, use the
button to lower the set temperature below the space temperature. The
flame symbol will disappear. Check that the heating plant does not
operate.
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Danfoss TP75-RF at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Danfoss TP75-RF in the language / languages: English as an attachment in your email.

The manual is 0.26 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Danfoss TP75-RF

Danfoss TP75-RF User Manual - English - 4 pages

Danfoss TP75-RF User Manual - German - 4 pages

Danfoss TP75-RF User Manual - Dutch - 4 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info