MODE CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/
SUB-TABLE CCN POINT PAGE NO.
OAU Outside Air Unit Config OAU_CFG 12
OA.TY Outdoor Air Unit Type 0=No OAU
1=ERV Module
2=Economizer
3=Pwr Exhaust
4=OA Monitor
5=100% OA
Unit
6=EXv1 ERV
0: no FIOP
1: FIOP EXv2
OAU_TYPE 40
OA.FC Outside Air Fan Curve 0 to 999 0: no FIOP
1: PG0307 1ph low
CFM ERV
2: PG0307 3ph low
CFM ERV
3: PG0307 1ph high
CFM ERV
4: PG0307 3ph high
CFM ERV
5: PG0814 low CFM
ERV
6: PG0814 high CFM
ERV
7: PM1624 low CFM
ERV
8: PM1624 high CFM
ERV
9: PM28 low CFM ERV
10: PM28 high CFM
ERV
OAFANCRV 105
PE.FC Exhaust Air Fan Curve 0 to 999 0: no FIOP
1: PG0306 1ph low
CFM ERV
2: PG0307 3ph low
CFM ERV
3: PG0306 1ph high
CFM ERV
4: PG0307 3ph high
CFM ERV
5: PG0814 low CFM
ERV
6: PG0814 high CFM
ERV
7: PM1624 low CFM
ERV
8: PM1624 high CFM
ERV
9: PM28 low CFM
ERV
10: PM28 high CFM
ERV
PEFANCRV 105
U.RUN OAU Unoccupied Operation No/Yes NO UNOCCRUN 105
OAU.F Shut Down on Fan Failure No/Yes Yes FATALOAU 105
M.WHL Modulating Wheel Install No/Yes NO MODWHEEL 105
OA.MN Minimum Outside Air
CFM
0 to 32000 CFM 375: PG0307 low
CFM ERV
800: PG0307 high
CFM ERV
1000: PG0814 low
CFM ERV
2500: PG0814 high
CFM ERV
3000: PM1628 low
CFM ERV
4000: PM1624 high
CFM ERV
5000: PM28 high
CFM ERV
MINOACFM 95
DCV.M Min DCV Outside Air CFM 0 to 32000 CFM 100: PG0307 ERV
250: PG0814 low
CFM ERV
600: PG0814 high
CFM ERV
1000: PM1624 low
CFM ERV
1500: PM1624 high
CFM ERV, PM28 low
CFM ERV
2000: PM28 high
CFM ERV
MINDCVSP 95
PEX.C Power Exhaust Control 0=Offset CFM
1=BP
0 PEX_CTL 105
PE.OF Power Exhaust CFM Offset 17000 to
17000
CFM 200 EXOFFSET 95
BP.SP Building Pressure Setpnt 0.25 to 0.25 in H2O 0.05 OAU_BPSP 95
OA.TM Outside Air Tempering Disable/Enable Disable OATEMPER 95
TM.LO OA Tempring Lockout Temp 0 to 80 °F 60 OATMPLOC 95
TM.SP OA Tempring SAT Setpoint 35 to 80 °F 55 OATMPSPT 95
OAC.K Outside Air CFM k Factor 0.8 to 1.2 1.0 OACFM_K 105
EXC.K Exhaust Air CFM k Factor 0.8 to 1.2 1.0 EXCFM_K 105
48/50PG and PM
185


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Carrier 48 50PG C03-14 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Carrier 48 50PG C03-14 in the language / languages: English as an attachment in your email.

The manual is 9,71 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info