Maximum Modulation -----------------------------------------------
The Maximum Modulation is the highest signal the control
can send to modulate the boiler. For boilers with electronic
operators, the boiler’s input signal range may not match the
output signal range of the Heatronic 4000. Use the MAX MOD
setting in the Source (#) Menu to select an appropriate boiler
maximum modulation.
For 0 to 10 V (dc):
Maximum Modulation =
Boiler’s Maximum Input Signal
x 100%
10 V (dc)
For 4 to 20 mA:
Maximum Modulation =
Boiler’s Maximum Input Signal - 4mA
x 100%
16 mA
Example:
A boiler’s input signal range is 0 to 9 V (dc). The Heatronic
4000 control has an output signal range of 0 to 10 V (dc).
Maximum Modulation = 9 V x 100% = 90%
10 V
Control’s
Output
Signal
Range
Boiler’s
Input
Signal
Range
100%
10 V (dc)
9 V (dc)
0 V (dc)0 V (dc)
90%
Boiler’s
Maximum
Input
Signal
Maximum
Modulation
0%
EMS Signal Minimum
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
The EMS Signal Minimum is applicable for EMS temperature
type boilers that operate based on a 0-10 Vdc analog input
signal. This setting is to be set to the appropriate signal that
is defined by the boiler’s ignition control. This analog value
corresponds to the temperature value set with the EMS
Temperature Minimum setting.
EMS Temperature Minimum
----------------------
The EMS Temperature Minimum is applicable for EMS temperature
type boilers that interpret an analog value as a temperature.
This setting is to be set to the appropriate temperature that
is defined by the boiler’s ignition control. For a 0-10 Vdc EMS
boiler, this temperature value corresponds to the value set with
the Vdc Signal Minimum setting. For a 4-20 mA EMS boiler,
this temperature value corresponds to 4 mA.
EMS Temperature Maximum
- - - - - - - - - - - - - - - - - - - - - -
The EMS Temperature Maximum is applicable for EMS
temperature type boilers that interpret an analog value as
a temperature. This setting is to be set to the appropriate
temperature that is defined by the boiler’s ignition control. For
a 0-10 Vdc EMS boiler, this temperature value corresponds
to 10 Vdc. For a 4-20 mA EMS boiler, this temperature value
corresponds to 20 mA.
Maximum Boiler Outlet
- - - -- - - - - -- - - - - - -- - - - - -- - --
The control has the capability for each boiler outlet tempera-
ture to be monitored & limited. The MAX OUT setting sets
the maximum boiler outlet temperature. If the boiler outlet
temperature reaches the boiler outlet maximum, the boiler
is turned off. In order for the boiler to be able to be turned
on again, the boiler outlet temperature must drop 10°F (6°C)
below the boiler outlet maximum.
If MAX OUT is set to OFF, the control only monitors the boiler
outlet temperature.
Boiler Pump Post Purge - - - - - - - - - - - - - - - - - - - - - - - - - - --------------
This setting sets the amount of time the control operates the
boiler pump after the boiler is turned off. This will purge heat out
of the boiler, reducing stand-by losses, & also aid in reducing
“kettling”. The amount of time for the boiler pump post purge
is adjustable between 10 seconds & 20:00 minutes. Auto is
also available in which the control automatically determines
the amount of time based on the boiler mass.
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Heatronic 4000 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Heatronic 4000 in the language / languages: English as an attachment in your email.

The manual is 7,85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Heatronic 4000

Bosch Heatronic 4000 User Manual - French - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info